Front Access Liberty Products Valve Regulated Lead Acid
|
 |
 |
|
100 Ampere hours up to 600 Ampere hours
|
 |
 |
|
Front Access Design
|
 |
 |
|
Front Access Design
|
 |
 |
|
*
*
|
|
|
 |
The msEndur is the latest advancement in VRLA batteries for standby applications. By combining C&D ' s history of battery research and design with advanced MSE technology, C&D has created the msEndur - The True Long-Life Battery. The msEndur batteries are unmatched in power density with space saving module designs and have a 20-year design life that will reduce total cost of ownership.
|
|
 |
 |
|
Liberty Series 1000(R) Valve Regulated Lead Calcium Battery
|
 |
For standby applications (Unit capacity from 25 to 600 Ampere-hours)
|
 |
|
|
|
SPECIFICATIONS
|
|
Electrolyte at 77F (25C)
|
1.300 specific gravity nominal sulfuric acid
|
|
Syatem float voltages
|
2.25 - 2.27 Volts per cell
|
|
Life expectancy
|
10 years, full float service at 77& (25C)
|
|
Container and cover
|
High-impact, flame-retardant PVC Flammability retings; UL 94-VO; ASTM D-635, self extinguishing Oxygen Index > 32
|
|
Safety vent system
|
Low-pressure release valve with flash arrester
|
|
 |
 |
|
Note: AC Ripple current from the charger shall not exceed 5 percent of the 8-hour (ampere-hour) rating of the battery
|
|